Differences Between Gen 2 and Gen 3 Smart Room Sensors

There are differences between the Gen 2 Rev D Comfort / Vivid sensors and the the Gen 3 Rev A Comfort / Vivid sensors. The supported uplink channels and downlink registers are all listed in the corresponding TRM documents. The differences are summarized in this table.

Data Type

GEN 2 SMART ROOM SENSORS

REV D

T0004893, T0004885, T0004895, T0004896

GEN 3 SMART ROOM SENSORS

 REV A

T0006115, T0006116, T0006117, T0006118, T0006161, T0006162, T0006163, T0006164

Uplink Channels

Break-In

0x06 00 _ _

No longer featured

External Connector: Analog Input

Not featured

0x11 02 _ _  _ _

Ambient Light Intensity

Not featured

0x10 02 _ _

Downlink Registers

LoRaWAN Commissioning

0x00, 0x01, 0x02, 0x03, 0x04, 0x05

Read-back no longer supported

Net ID MSBs

0x19 _ _  _ _

No longer featured

Net ID LSBs

0x1A _ _  _ _

No longer featured

Break-In Threshold

0x30 _ _  _ _

No longer featured. 0x30 reassigned

Impact Alarm Event Threshold

0x31 _ _  _ _

0x30 _ _  _ _ (0x31 reassigned)

Acceleration Event Threshold

Not featured

0x31 _ _  _ _

Impact Alarm Event Grace Period

Not featured

0x36 _ _  _ _

Impact Alarm Event Threshold Count

Not featured

0x37 _ _  _ _

Impact Alarm Event Threshold Period

Not featured

0x38 _ _  _ _

Analog Input Sample Period: Idle State

Not featured

0x44 _ _  _ _  _ _  _ _

Analog Input Sample Period: Active State

Not featured

0x45 _ _  _ _  _ _  _ _

Low/High Analog Input Thresholds

Not featured

0x46 _ _  _ _  _ _  _ _

Analog Input Thresholds Enabled

Not featured

0x4A _ _